130 Series Venturi Balancing Valve

The key to precise and efficient heating

Stephanie Allchurch Product Development Manager at Altecnic
21.02.2023

Stephanie Allchurch, Product Development Manager at Altecnic, talks all things balancing to unlock the efficiency of any heating system.

System design

Many systems, including 2-pipe direct return, 2-pipe reverse return, and manifold-based distribution, use parallel circuits to deliver a portion of the total system flow rate to either individual zones within a building or individual heat emitters. Ideally, every zone or heat emitter in such systems would be identical to the others. Each would need to deliver the same rate of heating, and each would have identical branch piping. Thus, each would need an equal percentage of the total system flow rate. Such ideal systems seldom exist. Instead, a more typical system will contain several different sizes or types of heat emitters, connected to the heat source using different types, sizes, or lengths of tubing.

When such a system is turned on, the flow rate that develops within each branch will be determined by the hydraulic resistance of that branch in comparison to the others, as well as the circulator used. There is no assurance that the flow rate in any given branch will not be capable of delivering the necessary rate of heat transfer to the heat emitter. Such a system may be properly designed and installed, but without the follow up of proper balancing, its performance is likely to fall short of expectations.

Consequences of an imbalanced system

Whenever a heating system is designed, the intent is to deliver the proper rate of heat transfer precisely when and where it’s needed within a building. Without proper balancing hardware and adjustment, that goal is almost never achieved. The most obvious consequence of an improperly balanced system is lack of comfort. This lack of comfort is usually attributed to room air temperatures that are too low, too high, or both.

When some areas of a building cannot be warmed to the desired room air temperature, issues such as frozen piping, the appearance in shrinkage cracks in wood and drywall surfaces, condensation on windows and growth of mould and mildew can occur. Wasted heating energy due to higher heat losses.

Some other undesirable conditions that can result from improperly balanced systems include high flow velocities in piping components creating noise and possible erosion, excessive energy use by circulators due to overflow conditions, as well as circulators that operate at low efficiency, or circulators that operate at high differential pressure which increases the potential for thrust damage of bushings or bearings.

Finding a solution

To overcome these problems, it is normal practice to install various balancing devices. These include static balancing valves and dynamic balancing valves.

The designer of any system calculates the flow rate required to each terminal unit and selects the type and size of the balancing valve to control the flow based on the type of pumping system utilised (constant speed or variable speed). Variable speed pumps are more common today, due to their ability to vary the flow rate to meet demand. Thereby reducing flow rates around the system, reducing system heat losses, reducing pumping costs, thereby increasing system delta-T and system efficiency.

Static balancing valves or manual balancing valves are conventional valves suitable for use in constant flow rate circuits frequently in conjunction with 3-port valves or downstream of the differential pressure control valves in variable volume systems.

Dynamic balancing valves include:

Constant Flow Regulators: Modern automatic devices which respond to changes in differential pressure to maintain the design flow rate of the internal flow regulating cartridge.

Differential Pressure Control Valves (DPCVs):  Adjustable and respond to changes in differential pressure automatically, adjusting to maintain a stable differential pressure between the capillary insertion point and the valve body.

Pressure Independent Control Valves (PICVs): control differential pressure across themselves, allowing a stable flow rate to be set on the valve regardless of any differential pressure changes upstream of the valve. The addition of a control head, ON/OFF or modulating, allows the valve to become the terminal unit control valve.

Altecnic has an extensive range of balancing valves for both domestic and commercial applications with many features and benefits, full information for these can be found on altecnic.co.uk